Emergency lighting is the battery-backed lighting that comes on when utility power fails. Commercial buildings need it on egress paths so people can reach an exit. Most US jobs are written to NFPA 101 and UL 924, with a 90-minute runtime on the battery.

Shop the full catalog: Emergency Lighting.

Exit signs vs emergency lights vs combos

  • Exit signs mark the door. They do not light the floor by themselves. See our LED exit signs.
  • Emergency lights (dual-head units) light the corridor, stair, and discharge. Start with a mini or standard indoor head, then step up output for longer spacing.
  • Combo units put both in one housing at a door. Use them when a separate sign and a separate head would stack on the same wall.

How to choose dual-head emergency lighting

Pick the housing and lumen package for the room, then match wet vs indoor. All of the Westgate units below are 120/277V with at least 90 minutes of backup.

Model Best for Output Notes
EL-M2 Tight corridors, low ceilings About 200 lumens Smallest dual-head, white or black
EL-M1 Apartments and small commercial About 254 lumens Mini housing, white or black
EL-1 / EL-2A / EL-1D Typical offices and stairs About 240 lumens Standard indoor; EL-1D is the designer look
EL-1L Longer indoor spacing 1.2W heads White or black
EL-HO Warehouses, long corridors About 650 lumens High-output indoor
EL-EHO Large open floors About 1250 lumens Extra high-output indoor
EL-WP Garages and outdoor egress About 454 lumens IP65 wet location

What inspectors look for

Plan for at least 90 minutes of illumination on backup, monthly functional tests, and annual 90-minute tests. Damp-rated heads belong in typical interiors. Wet-location or enclosed heads belong in garages, wash-down, and outdoor egress. Letter color on exit signs (red vs green) follows local preference and code.

NFPA 101 wants the path of egress to average at least 1 footcandle, with no point below 0.1 footcandle, along the walking surface. High-output heads let you stretch spacing. Mini heads need tighter spacing. If you already have Westgate exit signs on the job, matching emergency heads keep the spec and the warranty in one brand. Call 765-473-5204 with a floor plan if you want a fixture count. For fixture spacing on the path of egress, see how to space emergency lights (1 footcandle average, 0.1 footcandle minimum).

Emergency lighting FAQ

How long does emergency lighting have to last?

Most commercial jobs in the US call for 90 minutes on battery. That is the UL 924 and NFPA 101 baseline for emergency lighting along the means of egress.

Do I need an exit sign and an emergency light?

Usually yes: the sign marks the door, the heads light the floor. A combo unit covers both at one location. Corridors and stairs still need separate emergency lights between exits.

Indoor vs wet-location emergency lighting

Use indoor dual-head units in conditioned corridors and rooms. Use a wet-location unit such as the EL-WP in parking garages, exterior discharge, and damp mechanical rooms.